LEADER 02116nam 2200373 450 001 996280679503316 005 20231206213926.0 010 $a1-5044-0216-2 024 7 $a10.1109/IEEESTD.1962.7378235 035 $a(CKB)3710000000568081 035 $a(NjHacI)993710000000568081 035 $a(EXLCZ)993710000000568081 100 $a20231206d1962 uy 0 101 0 $aeng 135 $aur||||||||||| 181 $ctxt$2rdacontent 182 $cc$2rdamedia 183 $acr$2rdacarrier 200 10$aIEEE Std 22A-1962 (Reaffirmed 1977) $eIEEE Guide for the Application of Interrupter Switches to Switch Capacitance Loads /$fInstitute of Electrical and Electronics Engineers 210 1$aPiscataway, New Jersey :$cIEEE,$d1962. 215 $a1 online resource (14 pages) 330 $aUsual Temperature and Altitude Service Conditions-Equipment conforming to this Standard shall be suitable for operation at its standard rating, provided that:(a) The temperature of the cooling air (ambient temperature) does not exceed 40C if the equipment has copper-to-copper contacts or equivalent.(b) The temperature of the cooling air (ambient temperature) does not exceed 55C if the equipment has all contacts silver surfaced or equivalent, and in addition has all conducting joints, including terminal connections, either (1) Separately held mechanically, and either soldered or silver surfaced, or (2) Brazed, welded or silver soldered and provided that such operation does not result in temperatures in excess of 90C for class O, 105C for class A or 130C for class ? insulations.( c ) The altitude does not exceed 3300 feet (1000 meters). 517 $aIEEE Std 22A-1962 606 $aElectric circuit-breakers$xStandards 606 $aElectric circuits$xAlternating current$xStandards 615 0$aElectric circuit-breakers$xStandards. 615 0$aElectric circuits$xAlternating current$xStandards. 676 $a620.110218 801 0$bNjHacI 801 1$bNjHacl 906 $aDOCUMENT 912 $a996280679503316 996 $aIEEE Std 22A-1962 (Reaffirmed 1977)$93646412 997 $aUNISA